i-NEXT DX 012 M1 S - 150 M4 D
Close control unit, INVERTER direct expansion air cooled
10,4 - 135 kW
-
format_align_leftDescriptionDuctable close control units air-conditioners for vertical installation and cooling only, with optional heating by means of heating element, optional humidifer and dehumidifier for precise temperature and humidity control. Particularly suitable for precision air conditioning in servers and IT rooms and all technological applications in general. The INVERTER compressor allows the cooling capacity modulation according to the real internal load, particularly efficient at the partial loads, optimizing the power absorbed and eliminating the stating current. Units fitted with electronic expansion valve and EC INVERTER fans, upflow or downflow.
Versions
- UNDER - Downflow air supply
- OVER - Upflow air supply
Features
- Unit for installing inside or outside the room to be air-conditioned.
- Last generation of scroll or rotary BLDC INVERTER compressor, for high efficiency.
- Standard COARSE 60% (ISO EN 16890) filtering section, Optional ePM10 50% (ISO EN 16890) - ePM1 85% (ISO EN 16890) , to CEN-EN 779 with average degree of separation 90.1% ASHRAE. The filter is self-extinguishing.
- Maximum resistance to rust thanks to galvanised sheet metal structures and panels with powder-coated paint finish. The panels are lined with sound-insulating material to limit noise levels.
- The reliability and functionality of the compressor and all the other parts are guaranteed by partners who are world leaders in their sector.
- NEW EC INVERTER fans with electronic commutation in order to maximize the energy saving and reducing the noise emissions. The fan section is contained within the machine and includes: centrifugal fans with backward curved blades with wing profile, single suction and without scroll housings (Plug-fans), directly coupled to external rotor EC electric motor brushless type with integrated electronic commutated system and continuous variation of the rotation speed.
- The microprocessor controls the compressor activation times with FIFO logic, thereby regulating the cooling capacity; it also controls the operating alarms with the possibility of interfacing to supervisor and remote-servicing systems.
- Switchboard to IEC 204-1/EN60204-1
- Refrigerant circuit consisting of electronic expansion valve that allows high performance and system efficiency thanks to a timely and accurate response to changes in temperature and pressure, sight glass, filter dryer on liquid line, pressure transducers with indication, control and protection functions, on low and high refrigerant pressure, high pressure safety switch with manual reset,liquid receiver with accessories.
- Capillary Pre and After sales service.
Accessories
- Remote user terminal
- Electric heating coil
- Humidifier
- Vibration isolation frame with rubber mountings
- Air distribution plenum
- Sound absorber plenum
- Interface electronic board
- UNDER - Downflow air supply
-
keyboard_hideContrôles
Control
- EVOLUTION+
Semi-graphic display 132 x 64 pixel, programmable software, record storage of 200 alarms, general alarm, automatic reset after blackout, integral LAN system, standby management,automatic rotation, serious alarms, operating contemporaneousness, clock function.
- EVOLUTION+
-
find_in_pageFiches Techniquesopenscroll to see all sizes
Application undefined
i-NEXT DX-OVER
Frame
Power supply
V/ph/Hz
PERFORMANCE
Total cooling capacity gross
(1)
kW
Sensible cooling capacity gross
(1)
kW
Total power input (Comp.+fans)
(1)
kW
EER (Indoor unit)
(1)
kW/kW
SHR
(2)
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
FANS
Fans type
Quantity
N°
Air flow
(3)
m³/h
NOISE LEVEL
Sound Power
dB(A)
Sound Pressure
(4)
dB(A)
SIZE AND WEIGHT
A
(3)
mm
B
(3)
mm
H
(3)
mm
Weight
(3)
kg
012 M1 S
018 M1 S
022 M1 S
030 M1 S
042 M2 D
047 M1 S
068 M2 D
094 M2 D
E1
E2
E3
E4
E5
E5
E7
E8
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
10,4
21,8
23,9
39,3
49,2
54,0
78,9
105
10,2
20,2
23,9
39,3
49,2
53,1
78,9
100
2,82
6,50
6,74
11,4
14,0
15,6
22,1
30,5
3,69
3,35
3,55
3,45
3,51
3,46
3,57
3,44
0,98
0,93
1,00
1,00
1,00
0,98
1,00
0,95
1
1
1
1
2
1
2
2
1
1
1
1
2
1
2
2
3,24
3,60
4,30
6,10
8,60
9,20
12,2
18,4
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
1
1
1
1
1
1
2
2
2800
4100
5500
10000
12000
12000
20000
22000
69
63
65
75
81
81
79
83
53
47
49
58
64
64
62
65
650
785
1085
1305
1630
1630
2175
2499
675
675
775
930
930
930
930
930
1925
1925
1925
1980
1980
1980
1980
1980
210
240
320
430
565
480
650
805
openscroll to see all sizesApplication undefined
i-NEXT DX-UNDER
Frame
Power supply
V/ph/Hz
PERFORMANCE
Total cooling capacity gross
(1)
kW
Sensible cooling capacity gross
(1)
kW
Total power input (Comp.+fans)
(1)
kW
EER (Indoor unit)
(1)
kW/kW
SHR
(2)
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
FANS
Fans type
Quantity
N°
Air flow
(3)
m³/h
NOISE LEVEL
Sound Power
dB(A)
Sound Pressure
(4)
dB(A)
SIZE AND WEIGHT
A
(3)
mm
B
(3)
mm
H
(3)
mm
Weight
(3)
kg
012 M1 S
018 M1 S
022 M1 S
030 M1 S
042 M2 D
047 M1 S
068 M2 D
094 M2 D
120 M4 D
150 M4 D
E1
E2
E3
E4
E5
E5
E7
E8
E9
E9
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
10,4
21,8
23,9
39,3
49,2
54,0
78,9
105
111
135
10,2
20,2
23,9
39,3
49,2
53,1
78,9
100
111
135
2,82
6,50
6,74
11,4
14,0
15,6
22,1
30,5
31,6
41,4
3,69
3,35
3,55
3,45
3,51
3,46
3,57
3,44
3,51
3,26
0,98
0,93
1,00
1,00
1,00
0,98
1,00
0,95
1,00
1,00
1
1
1
1
2
1
2
2
4
4
1
1
1
1
2
1
2
2
2
2
3,24
3,60
4,30
6,10
8,60
9,20
12,2
18,4
20,8
20,8
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
EC FAN
1
1
1
1
1
1
2
2
3
3
2800
4100
5500
10000
12000
12000
20000
22000
28000
32000
63
64
62
74
76
76
75
78
80
80
47
48
46
57
59
59
58
60
62
62
650
785
1085
1305
1630
1630
2175
2499
2899
2899
675
675
775
930
930
930
930
930
930
930
1925
1925
1925
1980
1980
1980
1980
1980
1980
1980
220
250
330
440
575
490
705
865
985
1010
-
picture_as_pdfTéléchargement
-
picture_as_pdf
GENERAL CATALOGUES
IT COOLING PRODUCT GUIDE
cloud_download
March 2020 -
picture_as_pdf
BROCHURES
IT COOLING PRODUCT OVERVIEW
cloud_download
January 2020 -
picture_as_pdf
BROCHURES
NEXT LEGACY
cloud_download
January 2020 -
picture_as_pdf
BROCHURES
RC FOR IT COOLING
cloud_download
June 2019 -
picture_as_pdf
PRODUCT OVERVIEW
IT COOLING OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
SELECTION SOFTWARE
ELCA WORLD
cloud_download
April 2020 -
picture_as_pdf
SELECTION SOFTWARE
AHU SELECTION SOFWARE
cloud_download
June 2019
-
picture_as_pdf
GENERAL CATALOGUES