WRX-Y 0162 - 0804
Reversible air cooled fully configurable high efficiency Rooftop units
50,8 - 240 kW
-
format_align_leftDescriptionStand-alone reversible air-to-air rooftop unit, for air treatment, filtration and renewal, in environments characterized by medium-large surfaces and volumes. The unit is equipped as standard with hermetic scroll compressors, a double independent refrigerant circuit, EC fan plug fans and electronic lamination valves. The structure is specific for outdoor installation, with base and supporting structure consisting of hot-dip galvanized steel sheet profiles of adequate thickness. The vertical structure and outer panelling are painted with polyester powders and the air treatment section is coated with a double layer insulating mat of adequate thickness. The unit, based on the selected configuration, allows the management of the Free-cooling mode with external, recirculation and ejection air motorized dampers. The unit is supplied in one or more modules to be assembled on site, to facilitate transport.
Configurations
- AR - Air recirculation function
- MF - Mixing and Free cooling function
- AX - Mixing and Free cooling function with Exhaust air Axial fan
- HR-F - Heat Recovery Free: air extractor fan(s), free cooling function and thermodynamic heat recovery from exhaust air flow
- HR-B - Heat Recovery Refrigerant Booster function: air extractor fan(s), free cooling function and heat recovery from exhaust air flow thanks to Refrigerant Booster coil
- HR-P - Heat Recovery Plate function: air extractor EC plugfan(s), free cooling function and heat recovery from exhaust air flow thanks to Plate (cross-flow) heat Exchanger.
- HR-E - Heat Recovery Enthalpy function: air extractor EC plug fan(s), free cooling function and heat recovery from exhaust air flow thanks to Rotary Enthalpic Wheel.
Features
- HIGH RELIABILITY
The wide working range, the double refrigerant circuit and the accurate design of the components ensure optimum performance with a continuous and constant operation also during heavy thermoigrometric conditions. - FLEXIBILITY
The unit is available with the opportunity to choose different supply and return airflows directions. - VERSATILITY
Different possibilities for the air treatment chambers; from total recirculation only to mixing with fresh air and extraction from the ambient with heat recovery. Each different configuration can be further customized thanks to a wide range of accessories. - HEAT RECOVERY FROM EXHAUST AIR FLOW
Units can be equipped with 4 different heat recovery systems: : thermodynamic on the exhaust air, thermodynamic type Refrigerant Booster (with additional refrigerant battery placed on the exhaust air flow), cross-flows or with enthalpy wheel. - PLUG-FAN VENTILATION
The supply and return plug fans combine the high efficiency of the ventilation section with an easy and fast installation of the unit, both electrical and aeraulic. - ELECTRONIC EXPANSION VALVE SUPPLIED STANDARD
The use of the electronic expansion valve generates considerable benefits, especially in cases of variable demand and different external conditions. It was introduced into these units as a result of accurate design choices concerning the cooling circuit and the optimisation of operation in various different working conditions
Accessories
- Enthalpy free-cooling
- Set-up for remote connectivity with ModBus/Echelon protocol cards
- Air flow regulation with CO2probe
- Integration or substitution heating resources: hot water heating coil, electrical heaters.
- Vair: variable air flow function, it allows to vary supply and return air flow according to the actual request of the HVAC system.
- AR - Air recirculation function
-
keyboard_hideContrôles
Control
- AIR3000TE
AIR3000TE is made up by two control boards, dedicated to the air side and the refrigerant side respectively. The LCD display has multi-level menu that allows for the monitoring and intervention on the unit. Thermoregulation is proportional to steps, referred to the return temperature; proportional-integral management can also be set. Its functions include the adjustment of the ambient humidity, the thermal or enthalpic (optional) free-cooling and supply temperature limitation. Defrosting is based on a self-adaptive propriety logic with monitoring of several operating and environmental parameters. The management of the ventilation can be realized with constant air flow or pressure regulation: as pressure drop varies, the fans change speed so as to maintain the flow-rate at the designed value. The controller independently manages several optional thermal resources and the amount of fresh air. The presence of the programmable timer allows the user to create an operating profile containing up to 4 typical days and 10 time bands. Diagnostics include complete alarm management, "black box" function (via PC) and alarm history (via display or even PC). Supervision can be developed via third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, ModBus-over-IP, Echelon LonWorks protocols. Compatibility with the remote keyboard managing up to 8 units.
- AIR3000TE
-
find_in_pageFiches Techniquesopenscroll to see all sizes
Application undefined
WRX-Y
Power supply
V/ph/Hz
COOLING ONLY (GROSS VALUE)
Total cooling capacity
(1)
kW
Total sensible capacity
(1)
kW
Compressors power input
(1)
kW
EER (total)
(1)(12)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(3)
kW
EER
(1)(3)
kW/kW
Cooling energy class
HEATING ONLY (GROSS VALUE)
Total heating capacity
(2)
kW
Compressors power input
(2)
kW
COP (total)
(2)(12)
kW/kW
HEATING ONLY (EN14511 VALUE)
Total heating capacity
(2)(3)
kW
COP
(2)(3)
kW/kW
Heating energy class
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c
(7)
kW
SEER
(7)(8)
Performance ηs
(7)(9)
%
SEASONAL EFFICIENCY IN HEATING (Reg. EU 2016/2281)
Ambient heating
PDesign
(7)
kW
SCOP
(7)(8)
Performance ηs
(7)(10)
%
SUPPLY FANS
Air flow rate
m³/h
Nominal ESP
(4)
Pa
Total power input
(12)
kW
REFRIGERANT CIRCUIT
No. Compressors/No. Circuits
N°
Refrigerant charge
(6)(11)
kg
NOISE LEVEL
Sound power level in cooling mode
(5)
dB(A)
Sound Power on outlet side
(5)
dB(A)
SIZE
Length A
(6)
mm
Width B
(6)
mm
Height H
(6)
mm
Operating weight
(6)
kg
0162
0182
0202
0262
0302
0352
0402
0444
0484
0524
0604
0704
0804
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
50,8
58,3
69,0
82,6
97,2
110
121
142
154
170
189
219
240
43,0
48,4
56,7
67,8
79,5
89,2
97,8
116
127
139
152
176
194
12,3
14,0
16,2
21,5
25,4
29,5
32,9
35,6
36,2
39,9
50,7
58,9
67,2
3,1
3,2
3,2
3,0
3,1
3,0
3,0
3,2
3,2
3,2
3,0
3,0
2,9
51,4
58,9
69,7
83,6
98,3
111
123
144
156
173
192
222
240
3,32
3,35
3,34
3,18
3,24
3,18
3,16
3,31
3,34
3,36
3,06
3,12
3,27
A
A
A
A
A
-
-
-
-
-
-
-
-
48,9
55,9
66,4
81,0
95,2
109
123
138
148
168
192
217
239
9,69
11,1
12,7
16,4
20,3
23,2
26,6
27,6
29,2
33,5
41,7
46,4
52,6
3,6
3,6
3,6
3,7
3,6
3,7
3,6
3,7
3,6
3,7
3,5
3,6
3,5
48,3
55,3
65,7
80,0
94,1
108
121
136
146
165
189
214
239
3,76
3,78
3,80
3,76
3,72
3,78
3,70
3,83
3,67
3,67
3,51
3,64
4,05
A
A
A
A
A
-
-
-
-
-
-
-
-
51,4
58,9
69,7
83,6
98,3
111
123
144
156
173
192
222
243
3,37
3,37
3,46
3,35
3,46
3,44
3,37
3,55
3,85
3,80
3,77
3,55
3,69
131,8
131,8
135,4
131,0
135,4
134,6
131,8
139,0
151,0
149,0
147,8
139,0
144,6
40,3
46,2
54,8
67,0
78,7
90,2
101
106
114
129
148
192
183
2,98
2,96
2,99
3,01
2,99
3,06
2,99
3,21
3,20
3,27
3,14
3,30
3,21
116,2
115,4
116,6
117,4
116,6
119,4
116,6
125,4
125,0
127,8
122,6
129,0
125,4
10500
12000
14000
16000
18500
21000
22500
27000
30000
32500
35000
41000
45000
200
200
200
250
250
250
300
300
350
350
350
350
350
1,93
2,49
2,61
2,85
3,11
3,63
4,05
4,76
5,24
5,88
6,60
7,46
8,86
2/2
2/2
2/2
2/2
2/2
2/2
2/2
4/2
4/2
4/2
4/2
4/2
4/2
14,0
19,0
20,0
20,0
27,0
30,0
33,0
40,0
43,0
54,0
53,6
56,0
59,0
77
79
82
83
84
86
87
85
86
86
86
89
90
80
83
81
82
82
82
84
85
87
88
88
88
0
3630
3630
3630
4080
4080
4080
4080
5560
5560
5560
5560
6460
6460
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2150
2150
2150
2150
2150
2150
2150
2150
2150
2150
2150
2150
2150
1270
1330
1350
1550
1650
1750
1850
2150
2340
2430
2430
3020
3170
-
picture_as_pdfTéléchargement
-
picture_as_pdf
GENERAL CATALOGUES
COMFORT PRODUCT GUIDE
cloud_download
May 2020 -
picture_as_pdf
GENERAL CATALOGUES
PROCESS PRODUCT GUIDE
cloud_download
March 2020 -
picture_as_pdf
BROCHURES
WRX-Y
cloud_download
May 2020 -
picture_as_pdf
BROCHURES
IT COOLING PRODUCT OVERVIEW
cloud_download
January 2020 -
picture_as_pdf
PROJECT FOCUS
CAPITEC
cloud_download
August 2020 -
picture_as_pdf
PROJECT FOCUS
TOYOTA MOTOR ITALIA
cloud_download
August 2020 -
picture_as_pdf
PRODUCT OVERVIEW
COMFORT OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
PRODUCT OVERVIEW
PROCESS OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
TECHNICAL DOCUMENTATIONS - REGULATION (EU) N. 2016/2281
WRX-Y 0162 - 0804 SCOP
cloud_download
May 2020 -
picture_as_pdf
TECHNICAL DOCUMENTATIONS - REGULATION (EU) N. 2016/2281
WRX-Y 0162 -0804 SEER
cloud_download
May 2020 -
picture_as_pdf
SELECTION SOFTWARE
ELCA WORLD
cloud_download
April 2020 -
picture_as_pdf
SELECTION SOFTWARE
AHU SELECTION SOFWARE
cloud_download
June 2019
-
picture_as_pdf
GENERAL CATALOGUES