i-NX-N-Y 0151P - 0502P
Reversible unit, air source for outdoor installation
43,9 - 128 kW
-
format_align_leftDescriptionOutdoor unit for the production of chilled/hot water with fixed speed and variable speed (Inverter Driven) Scroll compressors, optimized for R410A in a single-circuit configuration, axial-flow fans, condensing coil with copper tubes and aluminum fins and electronic expansion valve as standard equipment. Flexible and reliable unit; it easily adapts itself to different thermal load conditions thanks to the precise temperature control together with the use of inverter technology. The high performance’s level, both full and partial load, is achieved thanks to the accurate unit’s design and to the use of fixed speed motor together with variable speed (inverter) motor.
Versions
- - - Basic
- SL - Super-low noise version
Configurations
- - - Basic function
- D - Partial condensing heat recovery function
Features
- HIGH EFFICIENCY
Unit with high efficiency and reduced energy consumption, thanks to the inverter technology, contributing to lower operating costs and therefore achieving a quick return on investment. - VARIABLE PRIMARY FLOW
Energy saving due to variable pump speed management based on load demand and the variable flow assures the functioning of the units also with critical working conditions. - INTEGRATED HYDRONIC MODULE
The built-in hydronic module already contains the main water circuit components; it is available as option with single or twin in-line pump, for achieving low or high head, fixed or variable speed and buffer tank. - TWO SOUND EMISSION LEVELS
Two different acustic versions are available to fit specific application requirements.
Accessories
- Remote control keyboard (distance to 200m and to 500m)
- Set-up for remote connectivity with ModBus/Echelon protocol cards
- Compressor power factor correction
- Soft start
- Hydronic kit available in different configurations with 1 or 2 pumps fixed speed or variable speed and buffer tank
- VPF (Variable Primary Flow) system
- EC fans with electronic DC brushless motor
- LOW NOISE KIT (only on no silenced versions)
- User Limit Control (U.L.C.) allows the safe startup of the unit in critical conditions of water and air temperature.
- Night mode is a system setting to limit maximum noise level of the unit.
- Traditional coils with copper tubes and alluminium fins, also available with prepainted fins or Fin Guard Silver protective treatment.
- - - Basic
-
keyboard_hideContrôles
Control
- Electronic control W3000+
The brand new W3000+ controller offers advanced functions and algorithms. The Compact keypad, as standard equipment, features function controls and a complete LCD display for viewing data and activating the unit, via a multilevel menu, with settable display language. In addition to or as an alternative, the KIPlink is available - Keyboard In Your Pocket - is the innovative user interface based on WiFi technology that allows one to operate on the unit directly from the smartphone or tablet. Using KIPlink, it is possible to turn the unit on and off, adjust the set-point, plot the main operating variables, monitor in detail the status of the refrigerant circuits, the compressors, the fans and the pumps (if present) and display and reset the possible alarms. The regulation features the continuous modulation of capacity, based on sequential adjustment + DIP referring to the leaving water temperature( neutral zone adjustment +DIP on outlet temperature probe , for the 0151 size). Diagnostics include complete alarm management, with “blackbox” functions (via PC) and alarm log (display or PC) for best analysis of unit be haviour. The built-in clock can be used to create an operating profile containing up to 4 typical days and 10 time bands, essential for efficient programming of energy production. Optional proprietary devices can perform the adjustment of the resources in systems made of several units. Consumption metering and performance measurement are possible as well. The variable primary flow control is always available as per standard (VPF.E function). Supervision is available with different options, using proprietary devices or by integration into third party systems using ModBus, BACnet, BACnet-over-IP and Echelon LonWorks protocols. A dedicated wall-mounted keypad can be used for remote control of all the functions.
- Electronic control W3000+
-
find_in_pageFiches Techniquesopenscroll to see all sizes
Application undefined
i-NX-N-Y
Power supply
V/ph/Hz
PERFORMANCE
COOLING ONLY (GROSS VALUE)
Cooling capacity
(1)
kW
Total power input
(1)
kW
EER
(1)
kW/kW
ESEER
(1)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(2)
kW
EER
(1)(2)
kW/kW
ESEER
(1)(2)
kW/kW
Cooling energy class
HEATING ONLY (GROSS VALUE)
Total heating capacity
(3)
kW
Total power input
(3)
kW
COP
(3)
kW/kW
HEATING ONLY (EN14511 VALUE)
Total heating capacity
(2)(3)
kW
COP
(2)(3)
kW/kW
Cooling energy class
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Process refrigeration at high temperature
Prated,c
(4)
kW
SEPR HT
(4)(6)
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2015/1095)
Process refrigeration at medium temperature
Prated,c
(5)
kW
SEPR MT
(5)(6)
SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)
PDesign
(7)
kW
SCOP
(7)(8)
Performance ηs
(7)(9)
%
Seasonal efficiency class
(7)
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow
(1)
l/s
Pressure drop at the heat exchanger
(1)
kPa
HEAT EXCHANGER USER SIDE IN HEATING
Water flow
(3)
l/s
Pressure drop at the heat exchanger
(3)
kPa
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
NOISE LEVEL
Sound Pressure
(10)
dB(A)
Sound power level in cooling
(11)(12)
dB(A)
Sound power level in heating
(11)(13)
dB(A)
SIZE AND WEIGHT
Operating weight
(14)
kg
A
(14)
mm
B
(14)
mm
H
(14)
mm
0151P
0182P
0202P
0262P
0302P
0352P
0402P
0502P
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3/50
400/3/50
400/3/50
400/3/50
43,87
50,90
62,09
74,40
85,27
104,7
113,8
128,3
15,79
18,34
22,11
26,13
30,40
37,39
41,10
46,15
2,778
2,781
2,810
2,851
2,806
2,799
2,769
2,783
4,270
4,300
4,140
4,350
4,260
4,450
4,380
4,470
43,60
50,60
61,70
74,00
84,90
104,2
113,3
127,7
2,710
2,720
2,750
2,790
2,750
2,750
2,720
2,740
4,000
4,000
3,860
4,060
4,010
4,160
4,100
4,200
C
C
C
C
C
C
C
C
46,80
53,82
66,60
79,72
90,60
111,6
119,5
138,0
14,85
17,09
21,08
24,83
28,81
35,54
37,97
42,95
3,141
3,146
3,156
3,214
3,146
3,144
3,145
3,209
47,10
54,10
67,00
80,20
91,10
112,2
120,1
138,7
3,100
3,100
3,110
3,170
3,110
3,110
3,110
3,170
B
B
B
B
B
B
B
B
34,7
41,4
45,9
61,2
68,9
85,4
85,2
106
3,73
3,80
3,68
3,83
3,84
4,02
3,98
3,97
146
149
144
150
151
158
156
156
A+
A+
A+
A++
A++
-
-
-
2,098
2,434
2,969
3,558
4,078
5,008
5,442
6,137
37,2
38,2
40,9
42,0
36,2
39,0
38,8
38,4
2,259
2,598
3,215
3,848
4,373
5,387
5,768
6,659
43,1
43,6
48,0
49,1
41,6
45,1
43,6
45,2
1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
14,4
19,5
22,9
27,1
26,8
38,7
39,2
50,9
66
66
68
69
68
70
70
70
84
84
86
87
87
89
89
89
84
84
85
86
87
89
89
89
650
730
820
880
1030
1190
1210
1340
2000
2000
2625
2625
3250
3250
3250
3875
1350
1350
1350
1350
1350
1350
1350
1350
2070
2070
2070
2070
2170
2170
2170
2170
openscroll to see all sizesApplication undefined
i-NX-N-Y /SL
Power supply
V/ph/Hz
PERFORMANCE
COOLING ONLY (GROSS VALUE)
Cooling capacity
(1)
kW
Total power input
(1)
kW
EER
(1)
kW/kW
ESEER
(1)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(2)
kW
EER
(1)(2)
kW/kW
ESEER
(1)(2)
kW/kW
Cooling energy class
HEATING ONLY (GROSS VALUE)
Total heating capacity
(3)
kW
Total power input
(3)
kW
COP
(3)
kW/kW
HEATING ONLY (EN14511 VALUE)
Total heating capacity
(2)(3)
kW
COP
(2)(3)
kW/kW
Cooling energy class
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Process refrigeration at high temperature
Prated,c
(4)
kW
SEPR HT
(4)(6)
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2015/1095)
Process refrigeration at medium temperature
Prated,c
(5)
kW
SEPR MT
(5)(6)
SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)
PDesign
(7)
kW
SCOP
(7)(8)
Performance ηs
(7)(9)
%
Seasonal efficiency class
(7)
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow
(1)
l/s
Pressure drop at the heat exchanger
(1)
kPa
HEAT EXCHANGER USER SIDE IN HEATING
Water flow
(3)
l/s
Pressure drop at the heat exchanger
(3)
kPa
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
NOISE LEVEL
Sound Pressure
(10)
dB(A)
Sound power level in cooling
(11)(12)
dB(A)
Sound power level in heating
(11)(13)
dB(A)
SIZE AND WEIGHT
Operating weight
(14)
kg
A
(14)
mm
B
(14)
mm
H
(14)
mm
0151P
0182P
0202P
0262P
0302P
0352P
0402P
0502P
400/3+N/50
400/3+N/50
400/3+N/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
40,96
48,39
59,30
72,40
81,36
98,56
111,7
125,7
14,76
17,30
21,37
25,36
28,32
35,56
40,19
43,83
2,770
2,798
2,771
2,850
2,876
2,770
2,779
2,870
4,360
4,300
4,230
4,380
4,450
4,500
4,580
4,520
40,80
48,10
59,00
72,00
81,00
98,20
111,2
125,1
2,710
2,740
2,710
2,790
2,830
2,720
2,730
2,820
4,110
4,020
3,970
4,080
4,180
4,250
4,320
4,250
C
C
C
C
C
C
C
C
45,67
54,94
66,62
81,40
90,40
110,8
124,4
139,5
13,89
16,82
20,35
24,94
27,68
33,96
38,08
42,74
3,288
3,268
3,281
3,269
3,264
3,259
3,265
3,267
46,00
55,30
67,00
81,90
90,90
111,4
125,1
140,2
3,240
3,220
3,230
3,220
3,230
3,220
3,230
3,230
A
A
A
A
A
A
A
A
34,4
41,3
50,0
57,0
67,8
77,4
94,1
105
3,77
3,76
3,68
3,82
3,96
3,93
4,02
4,04
148
147
144
150
155
154
158
158
A+
A+
A+
A++
A++
-
-
-
1,959
2,314
2,836
3,462
3,891
4,713
5,341
6,010
32,4
34,6
37,3
39,8
33,0
34,6
37,3
36,8
2,205
2,652
3,216
3,929
4,364
5,348
6,004
6,732
41,1
45,4
48,0
51,2
41,5
44,5
47,2
46,2
1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
18,8
25,4
26,2
26,6
37,6
37,0
49,9
61,0
60
60
61
61
61
63
63
63
78
78
79
80
80
82
82
82
78
78
79
80
80
82
82
82
670
830
860
1010
1080
1260
1320
1460
2000
2625
2625
3250
3250
3875
3875
4500
1350
1350
1350
1350
1350
1350
1350
1350
2070
2070
2070
2170
2170
2170
2170
2170
-
picture_as_pdfTéléchargement
-
picture_as_pdf
GENERAL CATALOGUES
COMFORT PRODUCT GUIDE
cloud_download
May 2020 -
picture_as_pdf
GENERAL CATALOGUES
PROCESS PRODUCT GUIDE
cloud_download
March 2020 -
picture_as_pdf
BROCHURES
IT COOLING PRODUCT OVERVIEW
cloud_download
January 2020 -
picture_as_pdf
BROCHURES
I-NX-N-Y
cloud_download
January 2019 -
picture_as_pdf
PROJECT FOCUS
CAPITEC
cloud_download
August 2020 -
picture_as_pdf
PROJECT FOCUS
TOYOTA MOTOR ITALIA
cloud_download
August 2020 -
picture_as_pdf
PRODUCT OVERVIEW
COMFORT OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
PRODUCT OVERVIEW
PROCESS OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
TECHNICAL DOCUMENTATIONS - REGULATION (EU) N. 813/2013
I-NX-N-Y SCOP
cloud_download
December 2018 -
picture_as_pdf
SELECTION SOFTWARE
ELCA WORLD
cloud_download
April 2020 -
picture_as_pdf
SELECTION SOFTWARE
AHU SELECTION SOFWARE
cloud_download
June 2019
-
picture_as_pdf
GENERAL CATALOGUES