FX-W-G05 0551 - 1752
Water cooled chiller
124 - 401 kW
-
format_align_leftDescriptionIndoor unit for the production of chilled water featuring semihermetic screw compressors optimized to operate with low compression ratio and R513A, shell and tubes evaporator designed by Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. and shell and tube condenser and electronic expansion valve. Base and supporting structure is made of polyester painted galvanized steel. Eurovent certification. The unit results extremely compact, thanks to the peculiar construction layout, without base frame and panels, and extremely flexible to easily adapts itself to different thermal load conditions thanks to the precise thermoregulation The high performance’s level is achieved thanks to the accurate sizing of all internal components.
Configurations
- - - Basic function
- D - Partial condensing heat recovery function
- R - Total condensing heat recovery function
Features
- LOW GWP REFRIGERANT
New generation refrigerant R513A, with reduced greenhouse effect in comparison with traditional HFC refrigerants (Global Warming Potential GWP of R513A = 572, GWP of R134a = 1300 as per IPCC rev. 5th) and zero impact on the ozone layer. Not flammable (ASHRAE 34, ISO 817: class A1). - ErP READY
Thanks to the high level of efficiency at part load, the unit can meet and exceed the minimum energy efficiency threshold rated by the Seasonal Energy Efficiency Ratio SEER, in accordance with the eco-sustainable design requirements for all products using energy. For this reason, the unit represents the best choice for all the hydronic installations on the residential and commercial air conditioning systems. - MAXIMUM COMPACTNESS
Maximum compactness to achieve a very high flexibility in the design process and installation operations, offering a premium solution in case of reduced clearances or when retrofitting existing installations. - ELECTRONIC EXPANSION VALVE SUPPLIED STANDARD
The electronic expansion valve brings several benefits especially in case of variable thermal load conditions and source temperature. It improves the efficiency of the unit and reduces power consumption, and allows a faster ramp-up time and wider operating limits. - ADAPTABILITY
Adaptability at the building’s cooling request thanks to the continuous capacity regulation, assured by sophisticated control’s logic.
Accessories
- VPF (Variable Primary Flow) system
- Several devices for condensation´s control
- Set-up for remote connectivity with ModBus, Echelon, Bacnet, Bacnet over-IP.
- Touch Screen visual display
- KIPlink user interface
- Kit HWT, High Water Temperature
- - - Basic function
-
keyboard_hideContrôles
Control
- Electronic control W3000TE
W3000TE controller offers feature a large format keyboard with wide LCD display in order to ensure an easy access to the machine setup and a complete view of unit's status. The assessment and intervention on the unit is managed through a multi-level menu, with selectable user’s language. The led icons immediately show the operating status of the circuits. As alternative, the innovative KIPlink user interface allows one to operate on the unit directly from the smartphone or tablet. Complete alarm management system is available, with the “black-box” and the alarm history display functions. Optional proprietary devices can perform the adjustment of the resources in systems made of several units. Consumption metering and performance measurement are possible, and supervision can be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, LonWorks. Compatibility with the remote keyboard managing up to 8 units. The programmable timer manages a weekly schedule organised into time bands (up to 10 daily time bands associated with different operating set points) to optimise unit performance by minimising power consumption during periods of inactivity. The regulation operates on the water circuits featuring the step-wise regulation referred to the return water temperature with proportional logic. Optionally (VPF package), capacity modulation can be integrated with hydraulic flow modulation, thanks to inverter-driven pumps and to specific resources for the hydraulic circuit.
- Electronic control W3000TE
-
find_in_pageFiches Techniquesopenscroll to see all sizes
Application undefined
FX-W-G05
Power supply
V/ph/Hz
PERFORMANCE
COOLING ONLY (GROSS VALUE)
Cooling capacity
(1)
kW
Total power input
(1)
kW
EER
(1)
kW/kW
ESEER
(1)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(2)
kW
EER
(1)(2)
kW/kW
ESEER
(1)(2)
kW/kW
Cooling energy class
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c
(7)
kW
SEER
(7)(8)
Performance ηs
(7)(9)
%
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow
(1)
l/s
Pressure drop at the heat exchanger
(1)
kPa
HEAT EXCHANGER SOURCE SIDE IN REFRIGERATION
Water flow
(1)
l/s
Pressure drop at the heat exchanger
(1)
kPa
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
NOISE LEVEL
Sound Pressure
(3)
dB(A)
Sound power level in cooling
(4)(5)
dB(A)
SIZE AND WEIGHT
A
(6)
mm
B
(6)
mm
H
(6)
mm
Operating weight
(6)
kg
0551
0651
0751
0851
0951
1102
1302
1402
1502
1602
1752
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
124,3
140,5
166,3
198,2
221,7
252,4
285,1
311,9
345,2
366,2
400,6
25,50
28,41
35,57
40,52
46,10
51,04
56,86
64,04
71,26
76,05
86,66
4,875
4,947
4,671
4,894
4,809
4,949
5,011
4,873
4,842
4,812
4,621
5,970
5,950
5,960
5,940
5,930
6,320
6,240
6,220
6,120
6,110
6,090
123,9
140,1
165,8
197,5
220,8
251,4
284,1
310,7
344,2
365,1
399,2
4,710
4,780
4,500
4,720
4,630
4,770
4,840
4,690
4,690
4,660
4,480
5,530
5,510
5,480
5,460
5,440
5,730
5,670
5,630
5,600
5,630
5,580
B
B
C
B
C
B
B
B
B
B
C
124
140
166
198
221
251
284
311
344
365
399
5,37
5,37
5,36
5,40
5,35
5,64
5,62
5,58
5,61
5,61
5,57
207
207
206
208
206
218
217
215
216
217
215
5,944
6,719
7,954
9,479
10,60
12,07
13,63
14,91
16,51
17,51
19,16
19,8
19,7
27,6
33,0
41,2
41,0
38,5
46,1
32,0
36,0
43,0
7,133
8,045
9,611
11,37
12,75
14,45
16,29
17,90
19,83
21,06
23,19
22,1
25,9
31,0
27,0
26,5
22,7
26,6
29,3
33,0
28,9
24,8
1
1
1
1
1
2
2
2
2
2
2
1
1
1
1
1
2
2
2
2
2
2
24,0
34,0
32,0
59,0
57,0
47,0
68,0
66,0
63,0
91,0
116
75
75
76
76
76
78
77
78
78
78
78
92
92
93
93
93
95
95
96
96
96
96
2400
2600
2700
3000
3000
3000
3100
3100
3200
3200
3200
920
920
950
960
960
1100
1100
1100
1100
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
1600
1600
1600
1050
1110
1280
1450
1460
1710
1820
1990
2280
2430
2590
-
picture_as_pdfTéléchargement
-
picture_as_pdf
GENERAL CATALOGUES
COMFORT PRODUCT GUIDE
cloud_download
May 2020 -
picture_as_pdf
GENERAL CATALOGUES
PROCESS PRODUCT GUIDE
cloud_download
March 2020 -
picture_as_pdf
BROCHURES
FX-W / FX-W/H
cloud_download
April 2020 -
picture_as_pdf
BROCHURES
IT COOLING PRODUCT OVERVIEW
cloud_download
January 2020 -
picture_as_pdf
BROCHURES
WATER COOLED CHILLER RANGE COMFORT
cloud_download
June 2019 -
picture_as_pdf
BROCHURES
FX-W-G05
cloud_download
May 2019 -
picture_as_pdf
PROJECT FOCUS
CAPITEC
cloud_download
August 2020 -
picture_as_pdf
PROJECT FOCUS
TOYOTA MOTOR ITALIA
cloud_download
August 2020 -
picture_as_pdf
PRODUCT OVERVIEW
COMFORT OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
PRODUCT OVERVIEW
PROCESS OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
TECHNICAL DOCUMENTATIONS - REGULATION (EU) N. 2016/2281
FX-W-G05 SEER
cloud_download
October 2018 -
picture_as_pdf
SELECTION SOFTWARE
ELCA WORLD
cloud_download
April 2020 -
picture_as_pdf
SELECTION SOFTWARE
AHU SELECTION SOFWARE
cloud_download
June 2019
-
picture_as_pdf
GENERAL CATALOGUES