NX-G06 0614P - 1214P
Chiller, air source for outdoor installation
153 - 314 kW
-
format_align_leftDescriptionOutdoor unit for the production of chilled water with hermetic rotary Scroll compressors, low-GWP and ozone-friendly refrigerant R454B, axial-flow fans, braze-welded plate-type heat exchanger, micro-channel full-aluminum air coils and thermostatic expansion valve. The range is composed by units equipped with four compressors in tandem configuration on two independent refrigeration circuits.
Versions
- K - Key efficiency, compact version
- LN-K - Low Noise, Key efficiency and compact version
- SL-K - Super Low noise, Key efficiency and compact version
Configurations
- - - Basic function
- D - Partial condensing heat recovery function
Features
- LOW GWP REFRIGERANT
The new generation refrigerant R454B is the most eco-sustainable alternative to traditional refrigerant R410A, offering a 76% reduction in terms of GWP (Global Warming Potential GWP of R454B = 466, GWP of R410A = 1924 as per IPCC rev. 5th) and zero impact on the ozone layer. - MAXIMUM COMPACTNESS
This new range is available in the K version, that integrates the maximum compactness with a qualifying unit’s efficiency. This allow to achieve a very high flexibility in the design process as well as during the on-site installation operations, offering a premium solution in case of reduced clearances or when retrofitting existing installations. - ALUMINIUM MICRO-CHANNEL HEAT EXCHANGERS
The full aluminium micro-channel condenser coils deliver high efficiency whilst ensuring a reduced refrigerant volume and a lower unit weight. The e-coating protection (optional) grants the highest level of resistance to corrosion in any condition, even in the most aggressive environments. - WIDE OPERATING RANGE
Full load operation is ensured with outdoor air temperature up to 46°C, partial load operation is possible up to or even beyond 50°C. The unit can produce chilled water at negative temperature (down to -10°C of leaving water temperature). Dedicated accessories allow the unit operation down to -20°C of outdoor air temperature. - INTEGRATED HYDRONIC GROUP
The optional built-in hydronic module already contains the main water circuit components; it is available with single or twin in-line, for achieving both low or high head.
Accessories
- Microchannel coils with e-coating protection
- Traditional coils with copper tubes and alluminium fins, also available with prepainted fins or Fin Guard Silver protective treatment.
- Copper-Copper heat exchanger coils
- Electronic expansion valve
- Compressor power factor correction
- Soft start
- Compressor suction and discharge valves
- High and low pressure gauges
- DVVF and DVV2F devices for low air temperature operation
- Anti-intrusion grills
- Hydronic kit available in different configurations with 1 or 2 pumps fixed speed or variable speed and buffer tank
- EC fans with electronic DC brushless motor
- K - Key efficiency, compact version
-
keyboard_hideContrôles
Control
- Electronic control W3000TE
W3000TE Compact control features an easy-to-use interface and a complete LCD display that allows consulting and intervening on the unit by means of a multi-language menu (19 languages are available). The regulation is based on the patented “Quickmind” water temperature regulation logic uses self-adapting control to maintain flow temperatures and optimise performance even in low water content scenarios. As an alternative, the proportional or proportional-integral regulations are also available. The diagnostics comprises a complete alarm management system, with the “black-box” (via PC) and the alarm history display (via display or also PC) for enhanced analysis of the unit operation Optional proprietary devices can perform the adjustment of the resources in systems made of several units. Consumption metering and performance measurement are possible as well. Supervision can be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, LonWorks. Compatibility with the remote keyboard (up to 8 units). The programmable timer manages a weekly schedule organised into time bands to optimise unit performance by minimising power consumption during periods of inactivity. Up to 10 daily time bands can be associated with different operating set points. The defrosting (air source reversible unit only) follows a proprietary self-adaptive logic, which features the monitoring of several operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall energy efficiency.
- Electronic control W3000TE
-
find_in_pageFiches Techniquesopenscroll to see all sizes
Application undefined
NX-G06/K
Power supply
V/ph/Hz
PERFORMANCE
COOLING ONLY (GROSS VALUE)
Cooling capacity
(1)
kW
Total power input
(1)
kW
EER
(1)
kW/kW
ESEER
(1)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(2)
kW
EER
(1)(2)
kW/kW
ESEER
(1)(2)
kW/kW
Cooling energy class
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c
(7)
kW
SEER
(7)(8)
Performance ηs
(7)(9)
%
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow
(1)
l/s
Pressure drop at the heat exchanger
(1)
kPa
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
NOISE LEVEL
Sound Pressure
(3)
dB(A)
Sound power level in cooling
(4)(5)
dB(A)
SIZE AND WEIGHT
A
(6)
mm
B
(6)
mm
H
(6)
mm
Operating weight
(6)
kg
0614P
0714P
0814P
0914P
1014P
1114P
1214P
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
158,1
186,3
209,1
238,2
277,6
296,0
313,6
54,79
62,62
73,94
82,97
92,87
101,7
110,7
2,885
2,976
2,829
2,870
2,988
2,911
2,833
157,8
186,0
208,7
237,9
277,2
295,7
313,2
2,840
2,930
2,790
2,830
2,950
2,880
2,800
-
-
-
-
-
-
-
158
186
209
238
277
296
313
3,98
4,25
4,15
4,29
4,20
4,19
4,05
156
167
163
168
165
164
159
7,560
8,910
9,998
11,39
13,28
14,16
15,00
41,5
43,4
44,0
46,4
50,5
43,1
48,4
4
4
4
4
4
4
4
2
2
2
2
2
2
2
17,5
19,4
25,3
25,4
28,7
33,3
33,4
60
60
61
62
63
63
63
92
92
93
94
95
95
95
3160
3160
3160
3160
4335
4335
4335
2250
2250
2250
2250
2250
2250
2250
2170
2170
2170
2170
2170
2170
2170
1540
1560
1570
1740
2210
2240
2250
openscroll to see all sizesApplication undefined
NX-G06/LN-K
Power supply
V/ph/Hz
PERFORMANCE
COOLING ONLY (GROSS VALUE)
Cooling capacity
(1)
kW
Total power input
(1)
kW
EER
(1)
kW/kW
ESEER
(1)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(2)
kW
EER
(1)(2)
kW/kW
ESEER
(1)(2)
kW/kW
Cooling energy class
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c
(7)
kW
SEER
(7)(8)
Performance ηs
(7)(9)
%
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow
(1)
l/s
Pressure drop at the heat exchanger
(1)
kPa
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
NOISE LEVEL
Sound Pressure
(3)
dB(A)
Sound power level in cooling
(4)(5)
dB(A)
SIZE AND WEIGHT
A
(6)
mm
B
(6)
mm
H
(6)
mm
Operating weight
(6)
kg
0614P
0714P
0814P
0914P
1014P
1114P
1214P
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
153,4
178,1
199,9
225,6
263,1
278,8
307,5
54,40
64,11
74,39
86,12
94,42
104,3
110,7
2,820
2,778
2,687
2,620
2,787
2,673
2,778
153,0
177,7
199,6
225,2
262,7
278,5
307,1
2,780
2,740
2,650
2,590
2,750
2,650
2,740
-
-
-
-
-
-
-
153
178
200
225
263
279
307
3,96
4,24
4,20
4,22
4,16
4,13
4,21
155
167
165
166
163
162
165
7,335
8,515
9,560
10,79
12,58
13,33
14,70
39,1
39,7
40,3
41,6
45,3
38,2
46,5
4
4
4
4
4
4
4
2
2
2
2
2
2
2
17,5
19,4
25,3
25,4
28,7
33,3
33,4
54
54
55
56
57
57
58
86
86
87
88
89
89
90
3160
3160
3160
3160
4335
4335
4335
2250
2250
2250
2250
2250
2250
2250
2170
2170
2170
2170
2170
2170
2170
1590
1610
1610
1790
2260
2290
2300
openscroll to see all sizesApplication undefined
NX-G06/SL-K
Power supply
V/ph/Hz
PERFORMANCE
COOLING ONLY (GROSS VALUE)
Cooling capacity
(1)
kW
Total power input
(1)
kW
EER
(1)
kW/kW
ESEER
(1)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(2)
kW
EER
(1)(2)
kW/kW
ESEER
(1)(2)
kW/kW
Cooling energy class
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c
(7)
kW
SEER
(7)(8)
Performance ηs
(7)(9)
%
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow
(1)
l/s
Pressure drop at the heat exchanger
(1)
kPa
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
NOISE LEVEL
Sound Pressure
(3)
dB(A)
Sound power level in cooling
(4)(5)
dB(A)
SIZE AND WEIGHT
A
(6)
mm
B
(6)
mm
H
(6)
mm
Operating weight
(6)
kg
0614P
0714P
0814P
0914P
1014P
1114P
1214P
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
152,6
172,7
205,7
231,6
253,4
284,2
299,7
52,60
66,01
72,73
83,47
96,81
102,0
111,8
2,901
2,617
2,829
2,774
2,618
2,786
2,681
152,2
172,4
205,4
231,3
253,1
283,9
299,4
2,860
2,580
2,790
2,740
2,590
2,760
2,650
-
-
-
-
-
-
-
152
172
205
231
253
284
299
4,10
4,21
4,21
4,26
4,16
4,19
4,10
161
166
166
167
163
165
161
7,298
8,260
9,837
11,08
12,12
13,59
14,33
38,6
37,3
42,6
43,9
42,1
39,7
44,2
4
4
4
4
4
4
4
2
2
2
2
2
2
2
16,3
20,0
27,0
28,6
28,7
38,1
38,2
50
51
51
52
52
54
54
82
83
83
84
84
86
86
3160
3160
4335
4335
4335
5510
5510
2250
2250
2250
2250
2250
2250
2250
2170
2170
2170
2170
2170
2170
2170
1590
1610
1910
2080
2260
2640
2650
-
picture_as_pdfTéléchargement
-
picture_as_pdf
BROCHURES
NX-G06 / NX-N G06 2-4-COMPRESSOR UNITS
cloud_download
June 2020 -
picture_as_pdf
BROCHURES
IT COOLING PRODUCT OVERVIEW
cloud_download
January 2020 -
picture_as_pdf
GENERAL CATALOGUES
COMFORT PRODUCT GUIDE
cloud_download
May 2020 -
picture_as_pdf
GENERAL CATALOGUES
PROCESS PRODUCT GUIDE
cloud_download
March 2020 -
picture_as_pdf
PROJECT FOCUS
CAPITEC
cloud_download
August 2020 -
picture_as_pdf
PROJECT FOCUS
TOYOTA MOTOR ITALIA
cloud_download
August 2020 -
picture_as_pdf
PRODUCT OVERVIEW
COMFORT OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
PRODUCT OVERVIEW
PROCESS OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
TECHNICAL DOCUMENTATIONS - REGULATION (EU) N. 2016/2281
NX-G06 4-COMPRESSOR UNITS SEER (EC FANS; PLATES)
cloud_download
November 2019 -
picture_as_pdf
TECHNICAL DOCUMENTATIONS - REGULATION (EU) N. 2016/2281
NX-G06 4-COMPRESSOR UNITS SEER (PLATES)
cloud_download
November 2019 -
picture_as_pdf
R454B SUPPORTING DOCUMENTS
R454B MANUAL
cloud_download
October 2019 -
picture_as_pdf
SELECTION SOFTWARE
ELCA WORLD
cloud_download
April 2020 -
picture_as_pdf
SELECTION SOFTWARE
AHU SELECTION SOFWARE
cloud_download
June 2019
-
picture_as_pdf
BROCHURES