i-BX 004M - 035T
Chiller, air source for outdoor installation
4,30 - 35,1 kW
-
format_align_leftDescriptionOutdoor unit for the production of chilled/hot water with variable speed (Inverter Driven) Scroll compressors, optimized for R410A in a single-circuit configuration, axial-flow fans, condensing coil with copper tubes and aluminum fins, plate heat exchanger on water side and electronic expansion valve as standard equipment. Flexible and reliable unit; it easily adapts itself to different thermal load conditions thanks to the precise temperature control together with the use of inverter technology. The high performance’s level, both full and partial load, is achieved thanks to the accurate unit’s design and to the use of variable speed (inverter) motor. The chillers i-BX are used in many applications, even completely different from each other, suitable for comfort and industrial processes, without making any compromises.
Versions
- B - Basic
Features
- ErP READY
The highest level of efficiency at part load, thanks to the inverter technology, can meet and exceed the minimum seasonal efficiency for cooling, SEER, according with the eco-sustainable design requirements for all products using energy. For this reason, the unit represents the best choice for all the hydronic application on the residential and commercial markets. The unit is suitable also for industrial market, satisfying the seasonal energy performance ratio SEPR. - SYSTEM EFFICIENCY
The unit is designed as a system: all components are regulated using proprietary control’s logic for the highest efficiency. - HIGH EFFICIENCY AT PARTIAL LOAD
High seasonal efficiency in both heating and cooling mode, using DC inverter technology to modulate compressor operation and deliver the exact amount of energy based on the actual needs of the building. High efficiency for low energy consumption during the operating hours. - HIGH EFFICIENCY COMPONENTS
In terms of improving performance and reducing power consumption, the electronic thermostatic valve is an important component that maximises system efficiency, same for the choise the hydronic kit with inverter water pump and the modulating the fans speed as standard equipments. - WIDE OPERATING RANGE
Full load operation is ensured with outdoor air temperature up to 46°C during summer and down to -10°C of outdoor air temperature during winter. Production of evaporator leaving water temperature from -8°C to 20°C. - INTEGRATED HYDRONIC MODULE
The integrated hydronic include all the water circuit components (anti-freeze electrical heater on plate heat exchanger, air vents, flow switch, water filter, safety valve, EC water pumps, expansion tank) so as to optimize installation space, times and costs.
Accessories
- Remote keyboard
- Cascade management kit
- Copper-Aluminum heat exchanger coils with epoxy treatment
- Copper-Copper heat exchanger coils
- Buffer tank
- Serial card RS485 for ModBus
- Rubber anti-vibration mounting kit
- B - Basic
-
keyboard_hideContrôles
Control
- NADISYSTEM
The keypad features function controls and a complete LCD display for viewing data and activating the unit, via a multilevel menu. The remote keyboard kit wired indoor and outdoor temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and increasing the energy efficiency. The electronic board allows you to manage: -outdoor air temperature sensor on board for climatic curve -the built-in clock can be used to create an operating profile containing time bands for space cooling -night mode to limit the noise level of the units. Noise level is reduced limiting the maximum speed of the compressor and fans. -up to 4 units in cascade (with the accessories N-CM)
- NADISYSTEM
-
find_in_pageFiches Techniquesopenscroll to see all sizes
Application undefined
i-BX M
Power supply
V/ph/Hz
PERFORMANCE
COOLING ONLY (GROSS VALUE)
Cooling capacity
(1)
kW
Total power input
(1)
kW
EER
(1)
kW/kW
ESEER
(1)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(2)
kW
EER
(1)(2)
kW/kW
ESEER
(1)(2)
kW/kW
Cooling energy class
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c
(7)
kW
SEER
(7)(8)
Performance ηs
(7)(9)
%
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow
l/s
Available unit's head
(1)
kPa
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
NOISE LEVEL
Sound Pressure
(3)
dB(A)
Sound power level in cooling
(4)(5)
dB(A)
SIZE AND WEIGHT
A
(6)
mm
B
(6)
mm
H
(6)
mm
Operating weight
(6)
kg
004M
006M
008M
010
013
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
4,300
6,107
8,100
10,60
12,90
1,555
2,120
2,820
3,640
4,740
2,774
2,882
2,872
2,912
2,722
4,200
4,360
4,700
4,290
4,550
4,300
6,110
8,110
10,60
12,90
2,820
2,920
2,920
2,920
2,740
4,530
4,600
5,080
4,340
4,690
C
B
B
B
C
4,30
6,11
8,11
10,6
12,9
4,38
4,43
4,93
4,39
4,78
172
174
194
172
188
0,206
0,292
0,387
0,507
0,617
50,7
38,1
61,8
55,6
55,3
1
1
1
1
1
1
1
1
1
1
1,45
2,10
3,55
3,60
3,65
33
34
35
38
39
64
65
66
69
70
900
900
900
900
900
370
370
420
420
420
940
940
1240
1240
1240
75
80
95
110
125
openscroll to see all sizesApplication undefined
i-BX T
Power supply
V/ph/Hz
PERFORMANCE
COOLING ONLY (GROSS VALUE)
Cooling capacity
(1)
kW
Total power input
(1)
kW
EER
(1)
kW/kW
ESEER
(1)
kW/kW
COOLING ONLY (EN14511 VALUE)
Cooling capacity
(1)(2)
kW
EER
(1)(2)
kW/kW
ESEER
(1)(2)
kW/kW
Cooling energy class
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c
(7)
kW
SEER
(7)(8)
Performance ηs
(7)(9)
%
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow
l/s
Available unit's head
(1)
kPa
REFRIGERANT CIRCUIT
Compressors nr.
N°
No. Circuits
N°
Refrigerant charge
kg
NOISE LEVEL
Sound Pressure
(3)
dB(A)
Sound power level in cooling
(4)(5)
dB(A)
SIZE AND WEIGHT
A
(6)
mm
B
(6)
mm
H
(6)
mm
Operating weight
(6)
kg
010T
013T
015T
020T
025T
030T
035T
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
400/3+N/50
10,70
13,30
15,50
20,60
25,00
29,80
35,10
3,640
4,740
5,440
7,200
8,690
10,00
11,84
2,940
2,806
2,849
2,861
2,877
2,980
2,975
4,360
4,570
4,140
4,120
4,260
4,150
4,290
10,70
13,30
15,50
20,60
25,00
29,90
35,20
2,950
2,820
2,870
2,880
2,900
3,010
3,000
4,420
4,690
4,200
4,200
4,360
4,270
4,390
B
C
C
C
B
B
B
10,7
13,3
15,5
20,6
25,0
29,9
35,2
4,46
4,80
4,31
4,31
4,52
4,52
4,57
176
189
169
169
178
178
180
0,512
0,636
0,741
0,985
1,196
1,425
1,679
52,7
51,7
76,7
66,3
60,3
90,0
73,5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3,60
3,65
2,75
4,15
5,75
6,45
6,90
38
39
43
43
43
44
45
69
70
74
74
75
76
77
900
900
900
1450
1450
1450
1700
420
420
420
550
550
550
650
1240
1240
1390
1200
1700
1700
1700
110
125
135
190
250
270
305
-
picture_as_pdfTéléchargement
-
picture_as_pdf
GENERAL CATALOGUES
COMFORT PRODUCT GUIDE
cloud_download
May 2020 -
picture_as_pdf
GENERAL CATALOGUES
PROCESS PRODUCT GUIDE
cloud_download
March 2020 -
picture_as_pdf
BROCHURES
IT COOLING PRODUCT OVERVIEW
cloud_download
January 2020 -
picture_as_pdf
BROCHURES
I-BX 004 - 035
cloud_download
June 2019 -
picture_as_pdf
PROJECT FOCUS
CAPITEC
cloud_download
August 2020 -
picture_as_pdf
PROJECT FOCUS
TOYOTA MOTOR ITALIA
cloud_download
August 2020 -
picture_as_pdf
PRODUCT OVERVIEW
COMFORT OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
PRODUCT OVERVIEW
PROCESS OVERVIEW
cloud_download
March 2020 -
picture_as_pdf
TECHNICAL DOCUMENTATIONS - REGULATION (EU) N. 2016/2281
I-BX 004M - 035T SEER
cloud_download
July 2018 -
picture_as_pdf
SELECTION SOFTWARE
ELCA WORLD
cloud_download
April 2020 -
picture_as_pdf
SELECTION SOFTWARE
AHU SELECTION SOFWARE
cloud_download
June 2019
-
picture_as_pdf
GENERAL CATALOGUES